Teraco Data Centre UPS Backup Power

System Overview

This installation supports critical data centre infrastructure through multiple UPS systems supplied by Eaton, providing reliable standby backup power for essential operations.

UPS Infrastructure
  •   6 × 600 kVA UPS systems
  •   3 × 300 kVA UPS systems
  • These systems ensure uninterrupted power protection for mission-critical data centre loads.
Teraco digital Realty logo
Battery Installation
  •   Battery Type HRL12540W
  •   Total Batteries Installed 1200 units
  •   Battery Room Temperature 25°C (controlled environment)

The batteries were installed across three manufacturing batches as part of the original UPS battery banks.

Operational Performance

The 2013 batch of batteries (400 units) was replaced in 2024 after approximately 11 years of service.

Typical VRLA Expectations

  •   Design life 10 years
  •   Typical expected service life 7–8 years in UPS applications
  •   Actual achieved service life 11 years
The extended service life can largely be attributed to:
  •   Controlled battery room temperature
  •   Stable UPS charging conditions
  •   Data centre environmental control
  •   Routine monitoring and maintenance
Data centre Ups backup Power installion
Data centre Ups backup Power installion

Planned Replacement

The remaining batteries from 2014 and 2015 are scheduled for replacement during 2026, placing them at approximately:

  •   11–12 years of operational service

This continues to exceed the typical service expectations for VRLA batteries in UPS environments.

UPS Backup Power Installation

Conclusion

This installation demonstrates the long-term reliability of HRL12540W batteries in a mission-critical data centre environment.

Although the batteries carry a 10-year design life, they successfully achieved 11–12 years of operational service, exceeding the commonly expected 7–8-year lifespan in UPS applications.

Key Conditions Maintaining the following conditions was key to maximizing battery lifespan:
  • Stable ambient temperature (25°C)
  • Proper UPS charging conditions
  • Routine monitoring and preventative maintenance
  • Controlled data centre environment